Description
Environmental Monitoring
The combination of temperature sensor and water leakage allows to trigger combined actions or to send alarm messages. State values can be transmitted by various protocols (syslog, SNMP traps, emails). This way a control of the environmental conditions is possible at any time.
Cascadable
The xBus interface can be cascaded to any point on the network using a standard network cable. Connecting other xBus peripheries is possible over the two RJ45 ports on the front.
Measuring range
Temperature: -25°C to +60°C
Accuracy: +/- 0.5 ° C (typ) to +25 ° C | +/- 1°C (maximum) from -10°C to +60°C.
Digital inputs
1 input for water leakage cable
1 input for end-of-line termination
No external power supply
Up to 4 sensors can be connected directly in series with an ePowerSwitch Master or a VidioGuard. More sensors can be attached through the xBus Extender.
Easy installation
The installation and setup of the xBus module is very simple and requires no additional calibration. Using a mounting bracket, the installation at almost any location is possible.
Assigning names
A user-defined name (up to 32 characters) can be assigned to each xBus module using an ePowerSwitch or a VizioGuard. Each sensor is uniquely identifiable this way.
Graph
The analog measured values can be displayed in a diagram and the time interval between two measurements is set flexible.
Mounting
The sensor with its digital xBus interface is designed for easy and fast installation in a 19″ rack. The mounting angle is rotatable by 90 degrees to ensure flexibility in mounting the device.
- Environmental Monitoring1.02 MB
Product inquiry
Temperature sensor with signal conditioner
This xBus interface is used to connect our sensor cable for water leaks. It can be connected to any ePowerSwitch Master or VizioGuard.
- Cable break monitoring
- Cascadable up to 200 meter
- Digital transmission
- Input for water sensor cable
- No external power supply
- Standard RJ45 cable